Evaluation and increase of load capacity of on-load tap changing transformers for improvement of their regulating possibilities

Authors

DOI:

https://doi.org/10.15587/1729-4061.2015.39881

Keywords:

mathematical model, temperature of upper levels of oil, power transformer, loading capacity, on-load tap changing, non-sensitivity zone, optimal control

Abstract

Among measures, aimed at reduction of electric energy losses, usage of the transformers for power flows correction in electric networks is recommended as the most efficient means of energy losses reduction during its transmission. The efficiency of this method considerably increases when the process of power flows optimal control is carried out in automatic mode. For this purpose automatic regulators and systems of automatic control of transformation ratios of the transformers with on load tap changing have been developed.

However, electric energy losses reduction using optimal control of power flows in electric networks will become efficient only when technical states of the transformers and autotransformers, involved in the process of control must be satisfactory and their residual resource and current loading capacity must have certain reserve. For their determination it is necessary to create corresponding methods and means of on-line diagnostics of the transformers and autotransformers. It is obvious that they must use the possibility of modern hardware and software and be based on SMART GRID principles.

Mathematical model of the forecast temperature of upper levels of oil has been developed, among other parameters, the given model takes into account the coefficient of residual resource of the coolers.

For evaluation of technical state of the transformers cooling system the facilities of neuro-fuzzy models will be used, as a result, functional dependences between important factors are taken into consideration.

Neuro-fuzzy model of the transformers loading capacity, depending on the resource coefficient of its cooling system has been developed. It is shown that maximum usage of transformers loading capacity, if it operates within automatic control system of electric energy system, is realized by means of the mechanism of establishment of the corresponding non-sensitivity zone of on-load tap champing operation.

Coordination of transformers operation in the system of optimal control of power flows in EES is realized by setting parameters and non-sensitivity zones of SAC, determined taking into account loading capacity of the transformers. 

Author Biographies

Olga Buslavets, Ministry of Energy and Coal Industry of Ukraine 30 Khreshchatyk str., Kyiv, Ukraine, 01601

Deputy Head of the Department

Department of Electricity Sector Reforming and Functioning

Chief of Branch on Fuel and Energy Balances

Petro Lezhniuk, Vinnytsia National Technical University Khmelnytske shose str., 95, Vinnytsia, Ukraine, 21021

Doctor of Science (Engineering), Professor, Head of the Chair of Electric Stations and Systems

Chair of Electric Stations and Systems

Olexander Rubanenko, Vinnytsia National Technical University Khmelnytske shose str., 95, Vinnytsia, Ukraine, 21021

PhD, Assistant Professor

Department of Electric Stations and Systems

References

  1. Kholmsky, V. G. (1975). Calculation and optimization of electric networks modes. Moscow ENAC, 279.
  2. Siddiqui, A. S., Khan, S., Ahsan, S., Khan, M. I., Annamalai, A. (2012). Application of phase shifting transformer in Indian Network. 2012 International Conference on Green Technologies (ICGT), 186-191. doi: 10.1109/icgt.2012.6477970
  3. Zhelezko, Y. S. (2009). Loss of electricity. Reactive power. Power quality. Guide for practical calculations. Moscow ENAС, 456.
  4. Methodical guides to the analy0sis of technological losses of electric energy and selection of measures of their reduction (2014). Kyiv: GRІFRE, 89.
  5. Stognіy, B. C. (2010). Sustainable development of power sector and smart energy system. Proceedings of the Institute of Electrodynamics of National Academy of Sciences of Ukraine, Special issue, 6–9.
  6. Kirilenko, О. V., Prakhovnik, А. V. (2010). Sustainable energy: Challenges and ways of development. Proceedings of the Institute of Electrodynamics of National Academy of Sciences of Ukraine, Collection of works, Special issue, 10–16.
  7. Kirilenko, О. V., Prakhovnik, А. V. (2010). Information and intellectualization of control systems in energy sector: certain conclusions of the recent years. Technical electrodynamics, Special issue, 10–17.
  8. Bahadornejad, M. (2014). Intelligent Control of On-Load Tap Changing Transformer. IEEE Transactions on Smart Grid, 5 (5), 2255–2263. doi: 10.1109/tsg.2014.2329017
  9. Lopez-Fernandez, X. M., Ertan, H. B., Turowski, J. (2013). Transformers. Analysis, design and measurement. CRC Press. Taylor & Francis Group, 593.
  10. Alekseev, B. A. (2010). Large power transformers: state control in the process of operation and revision. Moscow: NТF «Energoprogress», 88.
  11. Rassalsky, A. M. Integrated approach to the diagnostics of high-voltage substation equipment 220–1150 kW under operating voltage in operation conditions. Electric engineering and electro mechanics, 4, 23–25.
  12. Gan, Y., Zhang, R. (2013). Distributed supervisory control solution for under-load tap-changing transformers. 2013 IEEE International Conference of IEEE Region 10 (TENCON 2013), 1–5. doi: 10.1109/tencon.2013.6718518
  13. Dolli, S. A.(2012). Modeling and optimal placement of voltage regulator for a radial system. 2012 International Conference on Power, Signals, Controls and Computation, 2012, 1–6. doi: 10.1109/epscicon.2012.6175262
  14. Aguero, J. R. (2012). Improving the efficiency of power distribution systems through technical and non-technical losses reduction. Transmission and Distribution Conference and Exposition (T&D) on, 1-8. doi: 10.1109/tdc.2012.6281652
  15. Zhuravlev, D. V. (2012). Technical measures for improvement the reliability of electric networks 330-500 kV operation. Energy and electrification, 11, 39–45.
  16. Buslavets, O. A., Kwitsinsky, A. O., Kudatsky, L. N., Lyakh, V. V., Mezhennaya, S. J., Molchanov, V. M., Stafіychuk, V. G.(2013). Determination of maximal load of transformer substations by calculation method. Energy and electrification, 5, 25–31.
  17. Lezhniuk, P. D., Rubanenko, A. E., Nіkіtorovich, O. V. (2012). Operational dіagnostics of high voltage equipment in the problems of optimal control of energy systems modes. Technical electrodynamics, 3, 33–36.
  18. Rubanenko, A. E., Kazmiruk, О. І. (2011). Control and improvement of loading capacity of the transformer. Visnyk of Vinnytsia Politechnical Institute, 6, 63–68.
  19. Agamalov, O. N., Kosterev, N. V., Lukash, N. P. et al. (2004). Application of fuzzy nonlinear autoregressive model with an external input for the assessment of electrical equipment state. Technical electrodynamics, 2, 49–58.
  20. Zhelezko, Yu. S., Artemyev, A. V., Savchenko, O. V. (2008). Calculation and analysis of energy losses in electrical networks. Moscow ENAС, 280.
  21. Babu, P. R., Sushma, B. (2013). Operation and control of electrical distribution system with extra voltage to minimize the losses. 2013 International Conference on Power, Energy and Control (ICPEC), 165–169. doi: 10.1109/ICPEC.2013.6527643

Downloads

Published

2015-04-10

How to Cite

Buslavets, O., Lezhniuk, P., & Rubanenko, O. (2015). Evaluation and increase of load capacity of on-load tap changing transformers for improvement of their regulating possibilities. Eastern-European Journal of Enterprise Technologies, 2(8(74), 35–41. https://doi.org/10.15587/1729-4061.2015.39881

Issue

Section

Energy-saving technologies and equipment