Diagnostics of the pre-fault situation of the bolted current-carrying joint in the conditions of changing regime parameters
DOI:
https://doi.org/10.15587/2312-8372.2019.157865Keywords:
weakening of bolted current-carrying joint, state diagnostics, random and deterministic mode of load currentAbstract
The object of research is the methods of non-destructive monitoring of the state of a bolted current-carrying joint under conditions of dynamically changing current load conditions and ambient temperature. One of the most problematic places in the modern conditions of economic development of enterprises is the reduction in the accident rate of production due to the weakening of the bolted current-carrying joint. Studies of the causes of stopping electrical equipment at a number of ferrous metallurgy enterprises, mining and processing complexes, in medical institutions have shown that in 1.5-2 % of cases the cause of an emergency shutdown of electrical equipment is the weakening of the bolted current-carrying joint. The main problem of the bolted current-carrying joint is the mechanical weakening of the contact density. The appearance of a temperature gradient in the place of a bolted joint is influenced by climatic parameters and dynamically changing modes of operating current loads and network voltage.
The study of operating parameters of the network and load currents is based on the use of a technique for monitoring the quality of electricity indicators using self-recording spectrum analyzers. In this study, the spectrum analyzer Fluk 435 (Ukraine) is used, the characteristics of which correspond to the ISO 9001 measurement system certificate. Statistical processing methods are used as the basis for processing the experimentally obtained data.
In the course of the study, the inequality between the measured temperature of the bolted current-carrying joint and the calculated temperature of the serviceable joint is determined. The inequality is fulfilled in the sections, the stationarity of which is determined for deterministic and random modes of change of the controlled parameters. The functions of Boolean variables are compiled, the disjunctive functions that determine the normal and pre-crash modes of the bolted joint are minimized. The obtained theoretical results allow developing algorithms and devices for diagnosing and protecting equipment.
This provides the opportunity to reduce the accident rate of the equipment. Compared with similar well-known protection equipment, taking into account the modes of load currents, mains voltage and ambient temperature provides a high sensitivity and accuracy of detecting the initial moment of loosening of a bolted current-carrying joint.
References
- Krivonosov, V. E., Zlepko, S. M., Virozub, R. M., Baranovskiy, D. M. (2017). Kriterii diagnostiki vintovykh soedineniy v ul'trazvukovoy tomograficheskoy apparature. Vіsnik Khmel'nits'kogo natsіonal'nogo unіversitetu. Serіya: Tekhnіchnі nauki, 1, 52–57.
- Kryvonosov, V. E. (2015). Pat. No. 107749 UA. Sposib kontroliu za stanom boltovykh ziednan elektroobladnannia, shcho pratsiuie zi zminnym navantazhenniam. MPK: G01N 27/24, H02K 15/12, G01N 25/72, H02H 5/04, H01R 31/00, G01N 27/20, G01R 13/00. No. a 201309491; declareted: 29.07.2013; published: 10.02.2015; Bul. No. 3, 4.
- Brady, J. (2011). Thermal Patterns Associated with Infrared Inspection of Electrical Systems. Available at: https://www.irinfo.org/05-01-2011-brady/
- Izmaylov, V. V., Naumov, A. E. (2008). Avtomatizirovannaya sistema prognozirovaniya ostatochnogo resursa elektrokontaktnykh soedineniy. Programmnye produkty i sistemy, 2, 73–75.
- A guide to low resistance testing (2017). Available at: https://www.techrentals.com.au/pdf_files/Megger_A_20Guide_20to_20Low_20Resistance_20Testing.pdf
- Kaplya, N. G., Kaplya, E. N. (2010). Pat. No. 2408120 RU. Ustroystvo dlya kontrolya temperatury kontaktnykh soedineniy v ustroystvakh, nakhodyashhimsya pod vysokim napryazheniem. MPK: H02H5/04. No. 2009115534/07; declareted: 24.04.2009; published: 27.12.2010; Bul. No. 36, 5.
- Genutis, D. A. (2006–2007). Infrared Inspections and Applications. NETA WORLD Winter. Available at: https://studylib.net/doc/18260220/infrared-inspections-and-applications
- Pat. No. CN 102636686 A (2012). Electrical heating tube detection device. 15.08.2012. Available at: https://patents.google.com/patent/CN203526081U/en
- Teslia, Yu. A., Diachenko, M. D. (2014). Pat. No. 104546 UA. Prystrii avtomatychnoho monitorynhu stanu kontaktnykh ziednan vysokovoltnykh pidstantsii i linii elektroperedach. MPK: H02H 5/04, H02G 15/12, H01R 13/02, H02G 15/08, G05B 19/05. No. a201301914; declareted: 18.02.2013; published: 10.02.2014; Bul. No. 3.
- Kennedy, R., Hope, J. (2013). Pat. No. 13/689340 USA. Dynamic Thermal Mapping. MPK: 702/64, 361/689. No. 20130138371; declareted: 29.11.2012; published: 30.05.2013.
- Kryvonosov, V. E., Pirotti, Ye. L. (2018). Pat. No. 127922 UA. Prystrii diahnostuvannia oslablennia boltovykh strumoveduchykh ziednan i obryvu strumoveduchykh chastyn systemy elektropostachannia elektropryimacha. MPK: H02H 5/04, H02K 15/12 / No. u201802711_2; declareted: 19.03.2018; published: 27.08.2018; Bul. No. 16, 4.
- Chistyakov, V. I. (1978). Kurs teorii veroyatnosti. Moscow, 224.
Downloads
Published
How to Cite
Issue
Section
License
Copyright (c) 2019 Valerii Kryvonosov
This work is licensed under a Creative Commons Attribution 4.0 International License.
The consolidation and conditions for the transfer of copyright (identification of authorship) is carried out in the License Agreement. In particular, the authors reserve the right to the authorship of their manuscript and transfer the first publication of this work to the journal under the terms of the Creative Commons CC BY license. At the same time, they have the right to conclude on their own additional agreements concerning the non-exclusive distribution of the work in the form in which it was published by this journal, but provided that the link to the first publication of the article in this journal is preserved.