Development of unit for radio frequency interference limits testing of high-voltage insulators

Authors

  • Володимир Олександрович Бржезицький National Technical University of Ukraine «Kyiv Polytechnic Institute», 37, Prospect Peremohy, 03056, Kyiv-56, Ukraine https://orcid.org/0000-0002-9768-7544
  • Ярослав Олександрович Гаран National Technical University of Ukraine «Kyiv Polytechnic Institute», 37, Prospect Peremohy, 03056, Kyiv-56, Ukraine https://orcid.org/0000-0003-3242-9218
  • Микола Юрійович Лапоша National Technical University of Ukraine «Kyiv Polytechnic Institute», 37, Prospect Peremohy, 03056, Kyiv-56, Ukraine https://orcid.org/0000-0003-0909-7876

DOI:

https://doi.org/10.15587/2312-8372.2016.59092

Keywords:

radio frequency interference limits, insulator, air line, noise of the unit, selective microvoltmeter

Abstract

Requirements for structural scheme and features unit for radio frequency interference limits testing of high-voltage insulators are considered.

The basic scheme of developed unit and method for radio frequency interference limits testing of high-voltage insulators according to intergovernmental standards are described.

Minimum unit parameters K+A=22 dB (mode 0,5 MHz) and K+A=21 dB (mode 1 MHz), which measurement is performed not separately but as a sum immediately, providing high stability results, are achieved.

The data of measuring the level of external interference (noise of the unit) and the conditions of its use are given.

Materials of the article may be useful for the development of high voltage equipment, oriented to the requirements of international standards.

Author Biographies

Володимир Олександрович Бржезицький, National Technical University of Ukraine «Kyiv Polytechnic Institute», 37, Prospect Peremohy, 03056, Kyiv-56

Doctor of Technical Sciences, Professor, Acting Head of Department

Department of High Voltage Engineering and Electrophysics

Ярослав Олександрович Гаран, National Technical University of Ukraine «Kyiv Polytechnic Institute», 37, Prospect Peremohy, 03056, Kyiv-56

Engineer

Department of High Voltage Engineering and Electrophysics

Микола Юрійович Лапоша, National Technical University of Ukraine «Kyiv Polytechnic Institute», 37, Prospect Peremohy, 03056, Kyiv-56

PhD student

Department of High Voltage Engineering and Electrophysics

References

  1. Burgsdorf, V. V., Zhuravlev, E. N. (1966). Radiopomehi ot linii elektroperedach sverhvysokogo napriazheniia i vybor secheniia provodov. Izvestiia AN SSSR. Energetika i transport, 5.
  2. In: Burgdorf, V. V.; Translated from English: Nikiforov, E. P., Savvaitov, D. S., Shleifman, M. B. (1980). Transmission line reference book, 345 kV and above. Moscow: Energiia, 408.
  3. IEC 60383-1. Insulators for overhead lines with a nominal voltage above 1000 V. Ceramic or glass insulator units for a. c. systems. Definitions, test methods and acceptance criteria. (1998). The British Standards Institution, 111. doi:10.3403/02205940u
  4. CISPR/TR 18-2. Radio interference characteristics of overhead power lines and high-voltage equipment. Methods of measurement and procedure for determining limits. (2010). The British Standards Institution, 76. doi:10.3403/30202393
  5. Reddy, B. S., Kumar, U. (2010, July 8). Radio interference measurements on a ceramic disc insulator string with field reduction electrode. Journal of Instrumentation, Vol. 5, № 07, T07001–T07001. doi:10.1088/1748-0221/5/07/t07001
  6. McMillan, F. O. (1932, January). Radio interference from insulator corona. Electrical Engineering, Vol. 51, № 1, 3–9. doi:10.1109/ee.1932.6429572
  7. Costea, M., Băran, I. (2010). Radiofrequency disturbances radiated and injected in a power line by a high voltage equipment. Scientific Bulletin of the Electrical Engineering Faculty of the Polytechnic University of Bucharest, Vol. 12, № 1, 77–83.
  8. Da Frota Mattos, M. K., Biagioni, P. H., Bassi, W. (1996). Electric field measurement on time domain generated by corona on insulators on distribution systems. Conference Record of the 1996 IEEE International Symposium on Electrical Insulation, Vol. 1, 328–330. doi:10.1109/elinsl.1996.549348
  9. Reddy, B. S., Kumar, U., Nath, D. (2012). Correlation between corona current and radio interference due to high voltage insulator string. IEEE 2012 Electrostatics Joint Conference. Cambridge, Ontario, Canada, 1–5.
  10. IEC 60437. Radio interference test on high-voltage insulators. (1998). The British Standards Institution, 36. doi:10.3403/01268403u
  11. GOST 26196. Izoliatory. Metod izmereniia industrial'nyh radiopomeh. (1997). Moscow: Publishing House of Standards, 4.
  12. IEC 60060-2. (2011). High-voltage test techniques. Measuring systems. British Standards Institution, 149. doi:10.3403/01670215u
  13. CISPR 16-1-1. Specification for radio disturbance and immunity measuring apparatus and methods – Part 1-1: Radio disturbance and immunity measuring apparatus – Measuring apparatus. (2015). IEC, 205.

Published

2016-01-21

How to Cite

Бржезицький, В. О., Гаран, Я. О., & Лапоша, М. Ю. (2016). Development of unit for radio frequency interference limits testing of high-voltage insulators. Technology Audit and Production Reserves, 1(1(27), 37–41. https://doi.org/10.15587/2312-8372.2016.59092

Issue

Section

Electrical Engineering and Industrial Electronics: Original Research