Alternative evaluation of voltage at top of transmission line tower stricken by lightning

Authors

DOI:

https://doi.org/10.15587/2706-5448.2021.228659

Keywords:

lightning flash, lightning performance, power line, wave reflection, oscillograms of real lightning currents

Abstract

The object of the research is a circuit that simulates a lightning strike to a tower of 220 kV power transmission line, taking into consideration the reflection of a current wave from 10 nearest towers. Computation of the voltage arising at the top of the stricken tower is necessary further to determine the lightning performance of transmission line by various methods. For Indian conditions, the average number of lightning strikes to this power line per 100 kilometers per year is about 77, which is a fairly high figure. As a rule, for the tasks of lightning protection, the lightning current is approximated by some analytical expression. In most cases, such expressions are various combinations of exponential functions. However, the waveform of real lightning currents on oscillograms differs significantly from the waveform attributed to them and approximated by relatively simple exponential expressions. For a more detailed study of transient processes caused by thunderstorm activity, there is a need to use oscillograms of real lightning currents when modeling.

The problem of determining the voltage at the top of the stricken transmission line tower was solved using circuit simulation. To simulate the lightning current, digitized oscillograms of real lightning currents with peak values of –5.256 kA and –133.586 kA were applied.

The article shows that the proposed approach gives a more accurate and visual representation of the transient process at the top of the stricken tower than the approximation of the lightning current by simple exponential expressions. Applying a simplified exponential description of the lightning current leads not only to a simplification of the nature of the transient process at the tower top, but also to an underestimation of the results to 8.8%. The selection of the equivalent circuit for the power line towers also affects the result. Representation of towers in the equivalent circuit with lumped inductances leads to slightly higher values compared to application of surge impedances in the circuit. In this case, the smaller the current amplitude, the greater the difference (8.6 % in the domain of low currents and 1.9 % in the domain of high currents). Since this leads to some reserve during the computations of lightning performance, it is recommended to use an equivalent circuit with lumped inductance for a transmission line tower.

The conducted research contributes to the development of methods for calculating the lightning performance of power lines and extends the scope of application of circuit simulation programs.

Author Biographies

Yevgeniy Trotsenko, National Technical University of Ukraine «Igor Sikorsky Kyiv Polytechnic Institute»

PhD, Associate Professor

Department of Theoretical Electrical Engineering

Mandar Madhukar Dixit, Vishwaniketan Institute of Management Entrepreneurship and Engineering Technology

Assistant Professor

Department of Electrical Engineering

Volodymyr Brzhezitsky, National Technical University of Ukraine «Igor Sikorsky Kyiv Polytechnic Institute»

Doctor of Technical Sciences, Professor

Department of Theoretical Electrical Engineering

Yaroslav Haran, National Technical University of Ukraine «Igor Sikorsky Kyiv Polytechnic Institute»

PhD, Assistant

Department of Theoretical Electrical Engineering

References

  1. Nath, A., Manohar, G. K., Dani, K. K., Devara, P. C. S. (2009). A study of lightning activity over land and oceanic regions of India. Journal of Earth System Science, 118 (5), 467–481. doi: http://doi.org/10.1007/s12040-009-0040-7
  2. Indian Standard IS 2309:1989, Protection of buildings and allied structures against lightning – Code of practice (Second Revision) (1991). Bureau of Indian standards, 64.
  3. Vaisala Annual lightning report 2020. Ref. B212260EN-A (2021). Vaisala. Available at: https://www.vaisala.com/sites/default/files/documents/WEA-MET-Annual-Lightning-Report-2020-B212260EN-A.pdf
  4. Holle, R. L. (2008). Annual Rates of Lightning Fatalities by Country. 20th International lightning detection conference, 1–14.
  5. Kamalapur, G. D., Sheelavant, V. R., Hyderabad, S., Pujar, A., Baksi, S., Patil, A. (2014). HVDC Transmission in India. IEEE Potentials, 33 (1), 22–27. doi: http://doi.org/10.1109/mpot.2012.2220870
  6. LaForest, J. J. (Ed.) (1982). Transmission line reference book (345 kV and above). Electric Power Research Institute. Palo Alto, 640.
  7. Halkude, S. A., Ankad, P. P. (2014). Analysis and Design of Transmission Line Tower 220 kV: A Parametric Study. International Journal of Engineering Research & Technology, 3 (8), 1343–1348.
  8. Bazutkin, V. V., Kadomskaia, K. P., Kostenko, M. V., Mikhailov, Iu. A. (1995). Perenapriazheniia v elektricheskikh sistemakh i zaschita ot nikh. Saint Petersburg: Energoatomizdat. Otdelenie, 320.
  9. Melo, M. O. B. C., Fonseca, L. C. A., Fontana, E., Naidu, S. R. (1997). Lightning Performance of Compact Transmission Lines. International Conference on Power Systems Transients. Seattle, 319–324.
  10. Sargent, M. A., Darveniza, M. (1969). Tower Surge Impedance. IEEE Transactions on Power Apparatus and Systems, PAS-88 (5), 680–687. doi: http://doi.org/10.1109/tpas.1969.292357
  11. Datsios, Z. G., Mikropoulos, P. N., Tsovilis, T. E. (2019). Effects of Lightning Channel Equivalent Impedance on Lightning Performance of Overhead Transmission Lines. IEEE Transactions on Electromagnetic Compatibility, 61 (3), 623–630. doi: http://doi.org/10.1109/temc.2019.2900420
  12. Micro-Cap 12. Electronic Circuit Analysis Program. Reference Manual (2018). Sunnyvale: Spectrum Software, 1098. Available at: http://www.spectrum-soft.com/download/rm12.pdf
  13. De Conti, A., Visacro, S. (2007). Analytical Representation of Single- and Double-Peaked Lightning Current Waveforms. IEEE Transactions on Electromagnetic Compatibility, 49 (2), 448–451. doi: http://doi.org/10.1109/temc.2007.897153
  14. Trotsenko, Y., Brzhezitsky, V., Mykhailenko, V. (2019). Revised Effect of Inductive Voltage Drop Across Line Lead on Protective Level of Surge Arrester. 2019 IEEE 2nd Ukraine Conference on Electrical and Computer Engineering (UKRCON). Lviv, 341–344. doi: http://doi.org/10.1109/ukrcon.2019.8879939
  15. Trotsenko, Y., Brzhezitsky, V., Mykhailenko, V. (2020). Estimation of Discharge Current Sharing Between Surge Arresters with Different Protective Characteristics Connected in Parallel. 2020 IEEE 7th International Conference on Energy Smart Systems (ESS). Kyiv, 73–78. doi: http://doi.org/10.1109/ess50319.2020.9160296
  16. Hussein, A. M., Janischewskyj, W., Milewski, M., Shostak, V., Rachidi, F., Chang, J. S. (2003). Comparison of current characteristics of lightning strokes measured at the CN Tower and at other elevated objects. 2003 IEEE Symposium on Electromagnetic Compatibility. Symposium Record (Cat. No.03CH37446). Boston, 2, 495–500. doi: http://doi.org/10.1109/isemc.2003.1236651
  17. Narita, T., Yamada, T., Mochizuki, A., Zaima, E., Ishii, M. (2000). Observation of current waveshapes of lightning strokes on transmission towers. IEEE Transactions on Power Delivery, 15 (1), 429–435. doi: http://doi.org/10.1109/61.847285
  18. Rohatgi, A. (2020). WebPlotDigitizer. Version 4.4. Pacifica. Available at: https://automeris.io/WebPlotDigitizer
  19. IEC 60071-1:2011. Insulation co-ordination – Part 1: Definitions, principles and rules (2011). Geneva: IEC Central Office, 74.

Downloads

Published

2021-04-30

How to Cite

Trotsenko, Y., Dixit, M. M., Brzhezitsky, V., & Haran, Y. (2021). Alternative evaluation of voltage at top of transmission line tower stricken by lightning. Technology Audit and Production Reserves, 2(1(58), 33–39. https://doi.org/10.15587/2706-5448.2021.228659

Issue

Section

Electrical Engineering and Industrial Electronics: Reports on Research Projects