Automatic cleaning system of sample preparation of flue gas tester
DOI:
https://doi.org/10.15587/2312-8372.2015.37029Keywords:
filter, gas analyzer, sample, gas, valve, flow meter, flow, dust, cleaning, control, scheduleAbstract
It is shown a detailed description of the operation of the automatic cleaning at different modes and levels of concentration of dust and gas stream pollution of flue gas.
The basis of an automatic cleaning system of dust filters before gas analyzers based on the principle of a closed system of automatic control. The system constantly compares the real current flow rate with a fixed current pre-entered in the control unit. The control unit sends a signal to the switching system of solenoid valves when reducing the flow of the sample, due to contamination (clogging) of filters below a fixed level and with the help of flow booster begins to reverse blowing of dust filter from dust in the chimney.
During investigation it is found that the best operation mode of system actuation is a 25-30 % decrease in the expense of the nominal value of the primary sample flow while "clean" filter. Another important feature of the system is the choice of performance and power of flow boosters for blowdown. The power of flow booster was 1,5-2,0 kW during investigations on the smokestacks of coal boilers, TPC with the dust concentration of 120-150 mg/m3 with ensuring a flow rate of smoke samples in the range of 8-10 l/min.
The proposed system is simple in construction, does not require a significant investment for its implementation and provides automatic cleaning of dust filters without operator. Automatic cleaning of filter dust is recommended for stationary systems for monitoring the concentration of toxic components of flue gases for industry, energy, cement, brick and asphalt concrete plants, everywhere where the treatment and control of flue gas is carried out by gas analyzers.
References
- Blinov, V. A., Blinova, M. P.; applicant and patentee Novosibirsk Branch of Research and Practice Association "Health and Pathology". (28.02.1994). Avtomaticheskii probootbornik dlia otbora prob vozduha. Patent RF № 2008646: G01N 1/22. Appl. № 4841747/26; stated 21.06.1990. Available: http://ru-patent.info/20/05-09/2008646.html
- Kudriashov, V. V., Ivanov, E. S., Kur'ianov, M. V.; patentee Institute of Comprehensive Exploitation of Mineral Resources of the Russian Academy of Sciences (RAS IPKON). (20.05.2014). Aspirator-pyleprobootbornik. Patent RF № 2516622: MPK: E21F G01N/. № 2012141693; stated 02.10.2012. Available: http://bankpatentov.ru/node/595189
- Vartanov, A. Z., Ruban, A. D., Shkuratnik, V. L. (2009). Metody i pribory kontrolia okruzhaiushchei sredy i ekologicheskii monitoring. M.: Gornaia kniga, 640.
- Yushketova, N. A., Poddubnyi, V. A. (2007). Metod passivnogo otbora prob dlia monitoringa himicheskogo zagriazneniia atmosfernogo vozduha. Chast' 1. Teoreticheskie osnovy (obzor). Ekologicheskie sistemy i pribory, № 2, 3-10.
- Yushketova, N. A., Poddubnyi, V. A. (2007). Metod passivnogo otbora prob dlia monitoringa himicheskogo zagriazneniia atmosfernogo vozduha. Chast' 2. Prakticheskie aspekty (obzor). Ekologicheskie sistemy i pribory, № 3, 15-23.
- De Santis, F., Fino, A., Tiwari, S. et al.; In: Longhurst, J. W. S., Brebbia, C. A., Power, H. (2000). A performance of the open end tube diffusion sampler (Palmes sampler) for monitoring nitrogen dioxide. Air Pollution VIII. Boston: WIT Press, 419-429.
- Gerboles, M., Buzica, D., Amantini, L., Lagler, F. (2006). Laboratory and field comparison of measurements obtained using the available diffusive samplers for ozone and nitrogen dioxide in ambient air. Journal of Environmental Monitoring, Vol. 8, № 1, 112-119. doi:10.1039/b511271k
- Plaisance, H., Piechocki-Minguy, A., Garcia-Fouque, S., Galloo, J. C. (2004, February). Influence of meteorological factors on the NO2 measurements by passive diffusion tube. Atmospheric Environment, Vol. 38, № 4, 573–580. doi:10.1016/j.atmosenv.2003.09.073
- Poriev, V. A., Dashkovskyi, O. A., Myndiuk, Ya. L. et al.; In: Poriev, V. A. (2009). Analitychni ekolohichni prylady ta systemy. Vinnytsia: UNIVERSUM, 336.
- Primisky, V., Ivasenko, V., Kornienko, D. (2014). Adaptation features and emission standards execution control in the industry. Eastern-European Journal Of Enterprise Technologies, 3(1(69)), 8-15. doi:10.15587/1729-4061.2014.24973
- Korniienko, D. H. (09.10.2014). Avtomatychna systema pylovoi ochystky probo pidhotovky hazoanalizatoriv. Application for an invention № a201411028.
Downloads
Published
How to Cite
Issue
Section
License
Copyright (c) 2016 Дмитро Григорович Корнієнко, Владислав Пилипович Приміський
This work is licensed under a Creative Commons Attribution 4.0 International License.
The consolidation and conditions for the transfer of copyright (identification of authorship) is carried out in the License Agreement. In particular, the authors reserve the right to the authorship of their manuscript and transfer the first publication of this work to the journal under the terms of the Creative Commons CC BY license. At the same time, they have the right to conclude on their own additional agreements concerning the non-exclusive distribution of the work in the form in which it was published by this journal, but provided that the link to the first publication of the article in this journal is preserved.