HEAT AND MASS TRANSFER PROCESSES IN AIR-TO-AIR MEMBRANE RECUPERATIVE HEAT EXCHANGER IN SUMMER

Authors

  • М.І. Кордюков Technical Trainer Mitsubishi Electric in Ukraine, Radisheva st. 10/14, of.110, Kiev, Ukraine, 03680, Ukraine
  • В.І. Дешко National Technical University of Ukraine "Kiev Polytechnic Institute", 03056, Ukraine, Kiev, Borschahivs'ka st. 115, Kiev, 03056, Ukraine,
  • І.О. Суходуб National Technical University of Ukraine "Kiev Polytechnic Institute", 03056, Ukraine, Kiev, Borschahivs'ka st. 115, Kiev, 03056, Ukraine,

DOI:

https://doi.org/10.15673/0453-8307.1/2014.32643

Keywords:

heat recovery, moisture recovery, energy efficient ventilation, membrane heat exchanger, effectiveness, sensible heat, latent heat.

Abstract

The article describes experimental and calculated data on air temperature and moisture content before and after heat exchanger, heat fluxes and energy savings during summer period of 2013 in Kiev. According to the results of experimental studies using a membrane exchanger in summer can increase the recovered heat flux due to the latent heat up to 20 % as compared with sensible heat exchanger. Calculation methods in comparison with the actual effect give more significant reduction of energy consumption due to decreasing supply air moisture content – 78.5 % (for one day), the average for the summer season – 74.6 % (using IWEC data). Average actual effectiveness ratios for summer period are 73.2 % for the sensible heat, 63.8 % for latent heat and 71.0 % for total heat.

References

References

Deshko V.I., Sukhodub I.О., Nagornaya S.А. Effektivnost' utilizacii teploty v rekuperativnyh teploobmennikah sistem ventiljacii // Jenergetika i jelektrifikacija. 2010. № 12. S. 37-43.

Obespechenie komfortnyh uslovij dlja rekon-struiruemyh panel'nyh zdanij pri ispol'zova-nii sistem ventiljacii Lossnay / M.I. Kordjukov, V.I. Deshko, I.O. Sukhodub, E.A. Severin // Stroitel'nye konstrukcii. 2013. № 77. S. 238-243.

Deshko V.I., Krot I.O. Utilizacija teploty v sistemah ventiljacii // Novaja Tema. 2009. № 2. S. 9‑11.

Ivanov O.P., Tihomirov S.A. Analiz srokov okupaemosti plastinchatogo i rotornogo teplo-utilizatorov // Holodil'naja tehnika i kondicio-nirovanie. 2007. №1. S. 1-5.

Gusev A.E., Mitjukov N.V. Razrabotka pro-grammy dlja obosnovanija ustanovki rekuperatora v sisteme ventiljacii // Geoinzheniring. 2011. №1 (10). S. 20-24.

http://www.mitsubishi-aircon.com.ua

ASHRAE Handbook HVAC: Systems and Equipment // ASHRAE. Atlanta, 2008.

Besant R., Simonson C. Air-to-Air Exchangers // ASHRAE Journal. 2003. № 45. pp. 42-52.

www.meteoprog.ua/ua/fwarchive/Kyiv/

http://rp5.ua/Weather_archive_in_Kiev,_Zhuliany_(airport)

http://freemeteo.com/default.asp?pid=20&gid=703448&sid=333450&la=1&lc=5&nDate=13/8/2013

Vishnevskij E.P. K voprosu o sootnoshenii skrytoj i javnoj teploty // Zhurnal ≪S.O.K.≫. 2010. №1. – S. 78-81.