Estimation of voltage waveform at top of transmission line tower struck by lightning of negative and positive polarity
DOI:
https://doi.org/10.15587/2706-5448.2021.232821Keywords:
lightning flash, lightning performance, power line, wave reflection, oscillograms of real lightning currentsAbstract
The object of research is a circuit that simulates a lightning strike to a tower of 220 kV power transmission line, taking into consideration the reflection of a current wave from 10 nearest towers. Computation of the voltage arising at the top of the struck tower is necessary further to determine the lightning performance of transmission line by various methods. The lightning current has several maxima, in the case of a positive impulse polarity and, accordingly, several minima, in the case of a negative polarity, which are generally being called peaks. In addition, the lightning current impulse has a non-constant steepness in the entire area of current rise up to the first peak. The approximation of the real lightning current by simplified mathematical expressions cannot take into account all its real features. For a more detailed study of transient processes caused by thunderstorm activity, there is a need to use oscillograms of real lightning currents when modeling.
The problem of determining the voltage at the top of the stricken transmission line tower was solved using circuit simulation. For an in-depth study of how the shape of the lightning current impulse affects the shape of the voltage at the top of the tower struck, digitized oscillograms of real lightning currents were used. The simulation was carried out for 7 negative lightning impulses with the first peak varying from –33.380 kA to –74.188 kA. In the case of positive lightning, 3 oscillograms were used with the first peak varying from +38.461 kA to +41.012 kA.
The article shows that the shape of the front of the lightning current impulse and the amplitude of the first peak of the lightning current have a decisive effect on the maximum voltage value at the top of a power transmission line tower struck by lightning. The maximum voltage occurs precisely at the front of the current wave before the first peak of the lightning current. Therefore, the back flashover of the insulation from the tower to the phase conductor is most likely at a moment in time at the front of the current wave. By the time the maximum current is reached, the voltage at the top of the tower will be reduced by several tens of percent, compared to the maximum voltage at the tower, which occurs much earlier at the front of the current wave.
The conducted research contributes to the development of methods for calculating the lightning performance of power lines and extends the scope of application of circuit simulation programs.
References
- Hashimoto, S., Baba, Y., Nagaoka, N., Ametani, A., Itamoto, N. (2010). An equivalent circuit of a transmission-line tower struck by lightning. 2010 30th International Conference on Lightning Protection (ICLP). doi: http://doi.org/10.1109/iclp.2010.7845761
- Melo, M. O. B. C., Fonseca, L. C. A., Fontana, E., Naidu, S. R. (1997). Lightning Performance of Compact Transmission Lines. International Conference on Power Systems Transients (IPST'97). Seattle, 319–324.
- Mohajeryami, S., Doostan, M. (2016). Including surge arresters in the lightning performance analysis of 132kV transmission line. 2016 IEEE/PES Transmission and Distribution Conference and Exposition (T&D). doi: http://doi.org/10.1109/tdc.2016.7519906
- Fekete, K., Nikolovski, S., Knezevic, G., Stojkov, M., Kovac, Z. (2010). Simulation of lightning transients on 110 kV overhead-cable transmission line using ATP-EMTP. Melecon 2010 –2010 15th IEEE Mediterranean Electrotechnical Conference. doi: http://doi.org/10.1109/melcon.2010.5475950
- Kizilcay, M., Neumann, C. (2007). Backflashover Analysis for 110-kV Lines at Multi-Circuit Overhead Line Towers. International Conference on Power Systems Transients (IPST’07), 1–6.
- Asif, M., Lee, H.-Y., Park, K.-H., Shakeel, A., Lee, B.-W. (2019). Assessment of Overvoltage and Insulation Coordination in Mixed HVDC Transmission Lines Exposed to Lightning Strikes. Energies, 12 (21), 4217. doi: http://doi.org/10.3390/en12214217
- Berger, K. (1967). Novel observations on lightning discharges: Results of research on Mount San Salvatore. Journal of the Franklin Institute, 283 (6), 478–525. doi: http://doi.org/10.1016/0016-0032(67)90598-4
- Barker, P. P., Mancao, R. T., Kvaltine, D. J., Parrish, D. E. (1993). Characteristics of lightning surges measured at metal oxide distribution arresters. IEEE Transactions on Power Delivery, 8 (1), 301–310. doi: http://doi.org/10.1109/61.180350
- Narita, T., Yamada, T., Mochizuki, A., Zaima, E., Ishii, M. (2000). Observation of current waveshapes of lightning strokes on transmission towers. IEEE Transactions on Power Delivery, 15 (1), 429–435. doi: http://doi.org/10.1109/61.847285
- Trotsenko, Y., Brzhezitsky, V., Mykhailenko, V. (2020). Estimation of Discharge Current Sharing Between Surge Arresters with Different Protective Characteristics Connected in Parallel. 2020 IEEE 7th International Conference on Energy Smart Systems (ESS). Kyiv, 73–78. doi: http://doi.org/10.1109/ess50319.2020.9160296
- Trotsenko, Y., Dixit, M. M., Brzhezitsky, V., Haran, Y. (2021). Alternative evaluation of voltage at top of transmission line tower stricken by lightning. Technology Audit and Production Reserves, 2 (1 (58)), 33–39. doi: http://doi.org/10.15587/2706-5448.2021.228659
- Halkude, S. A., Ankad, P. P. (2014). Analysis and Design of Transmission Line Tower 220 kV: A Parametric Study. International Journal of Engineering Research & Technology, 3 (8), 1343–1348.
- Micro-Cap 12. Electronic Circuit Analysis Program. Reference Manual (2018). Sunnyvale: Spectrum Software, 1098. Available at: http://www.spectrum-soft.com/download/rm12.pdf
- Rohatgi, A. (2020). WebPlotDigitizer. Version 4.4. Pacifica. Available at: https://automeris.io/WebPlotDigitizer
- Moselhy, A. H., Abdel-Aziz, A. M., Gilany, M., Emam, A. (2020). Impact of First Tower Earthing Resistance on Fast Front Back-Flashover in a 66 kV Transmission System. Energies, 13 (18), 4663. doi: http://doi.org/10.3390/en13184663
Downloads
Published
How to Cite
Issue
Section
License
Copyright (c) 2021 Yevgeniy Trotsenko, Mandar Madhukar Dixit, Volodymyr Brzhezitsky, Yaroslav Haran
This work is licensed under a Creative Commons Attribution 4.0 International License.
The consolidation and conditions for the transfer of copyright (identification of authorship) is carried out in the License Agreement. In particular, the authors reserve the right to the authorship of their manuscript and transfer the first publication of this work to the journal under the terms of the Creative Commons CC BY license. At the same time, they have the right to conclude on their own additional agreements concerning the non-exclusive distribution of the work in the form in which it was published by this journal, but provided that the link to the first publication of the article in this journal is preserved.