Correction of characteristics of high-voltage test transformer
DOI:
https://doi.org/10.15587/2312-8372.2015.44269Keywords:
test transformer, leakage inductance, capacitance current, inductive voltage dropAbstract
Dependence of performances of serial high-voltage testing transformer ИОМ-100/25 with a measuring winding from character of a loading is explored. Substantial growth of a high voltage measuring error by means of measuring winding ИОМ-100/25 is fixed at a capacitive load.
The cause of a capacitive load effect on a measuring error of a high voltage for the given type of transformers and its analogues is defined – proportions of a leakage inductance of a measuring winding and all high-voltage winding do not coincide with the nominal division ratio for these windings, owing to design features of the given type of transformers.
The procedure of the high voltage measuring error correction defined by means of measuring winding ИОМ-100/25 (or analogous transformers), by means of compensation of the inductive voltage drop on measuring winding by the additional capacitor which is switched on in succession with a measuring winding is offered.
The results of the research can be used to upgrade the high voltage electrical testing laboratories.References
- Avrutskiy, V. A., Kuzhekin, I. P., Chernov, E. N. (1983). Ispyitatelnyie i elektrofizicheskie ustanovki. Tehnika eksperimenta. M.: MEI, 264.
- Kuffel, E., Zaengal, W. (2000). Preface to First Edition. High Voltage Engineering Fundamentals. Elsevier, 539. doi:10.1016/b978-075063634-6/50001-0
- Dyimkov, A. M. (1963). Transformatoryi napryazheniya. M.-L.: Gosenergoizdat, 192.
- Stepanchuk, K. F., Tinyakov, N. A. (1982). Tehnika visokih napryazheniy. Mn.: Vyish. shkola, 367.
- Brzhezytskyi, V. O., Haran, Ya. O. (2010). Osoblyvosti kharakterystyk vysokovoltnykh vyprobuvalnykh transformatoriv. Elektrotekhnika i elektromekhanika, 1, 36-37.
- Tułodziecki, B. (2011). High voltage test transformers, construction, design and their application in HV testing system. Electrical Review, Vol. 87, № 1, 195-198.
- Biricik, S., Özerdem, Ö. C. (2011). A Method for Power Losses Evaluation in Single Phase Transformers under Linear and Nonlinear Load Conditions. Electrical Review, Vol. 87, № 12, 74-77.
- Kaczmarek, M., Nowicz, R. (2010). Application of Instrument Transformers in Power Quality Assessment. Modern Electric Power Systems (MEPS). Proceedings of the International Symposium. Wroclaw, Poland, 34-38.
- Daut, I., Hasan, S., Taib, S. (2013). Magnetizing Current, Harmonic Content and Power Factor as the Indicators of Transformer Core Saturation. Journal of Clean Energy Technologies, 1 (4), 304–307. doi:10.7763/jocet.2013.v1.69
- Heathcote, M. J. (1998). The J & P Transformer Book. Oxford: Newnes, 945. doi:10.1016/B978-0-408-00494-7.50001-7
- Grudinskiy, P. G., Petrova, G. N., Sokolova, M. M., Fedoseeva, A. M., Chilikina, M. G. et al. (1974). Elektrotehnicheskiy spravochnik. Vol. 1. M.: Energiya, 776.
- Brzhezytskyi, V. O., Haran, Ya. O.; National Technical University of Ukraine "Kyiv Polytechnic Institute". (27.08.2013). Vysokovoltnyi vyprobuvalnyi transformator. Patent of Ukraine № 102864: MPK H01F 38/20, H01F 38/24/. Appl. № 201103746. Filed 28.03.2011. Bull. № 16, 4.
Downloads
Published
How to Cite
Issue
Section
License
Copyright (c) 2016 Володимир Олександрович Бржезицький, Ярослав Олександрович Гаран
This work is licensed under a Creative Commons Attribution 4.0 International License.
The consolidation and conditions for the transfer of copyright (identification of authorship) is carried out in the License Agreement. In particular, the authors reserve the right to the authorship of their manuscript and transfer the first publication of this work to the journal under the terms of the Creative Commons CC BY license. At the same time, they have the right to conclude on their own additional agreements concerning the non-exclusive distribution of the work in the form in which it was published by this journal, but provided that the link to the first publication of the article in this journal is preserved.