Influence of dry mixtures in a coating on the effectiveness of wood protection from the action of a magnesium flame

Authors

  • Yuriy Tsapko National University of Life and Environmental Sciences of Ukraine Heroiv Oborony str., 15, Kyiv, Ukraine, 03041 Kyiv National University of Construction and Architecture Povitroflotsky ave., 31, Kyiv, Ukraine, 03037, Ukraine https://orcid.org/0000-0003-0625-0783
  • Аleksii Tsapko National University of Life and Environmental Sciences of Ukraine Heroiv Oborony str., 15, Kyiv, Ukraine, 03041, Ukraine https://orcid.org/0000-0003-2298-068X

DOI:

https://doi.org/10.15587/1729-4061.2017.111106

Keywords:

metallic combustion, mass loss, charring, protective means for wood, extinguishing powders

Abstract

We carried out an analysis of the occurrence of fires and explosions on objects of storage of explosive products and established that one of the greatest risks is a fire hazard. Since the storage of such products involves the use of wood, both in building structures and packaging products, it is important to establish effectiveness of fire protection at high temperatures and influence of components that are part of the composition, and their role in ensuring fire resistance and fire protection mechanisms. This makes it possible to develop effective methods and means for extinguishing fires in such classes and take into account their peculiarities. We proposed a composition to counteract a high temperature. The basis of its mixture consisted of fire retardants (ammonium polyphosphate), gas formers (melamine), carbohydrates (pentaerythritol), and high-temperature fillers based on mineral substances. Studies showed that charring depth under the action of magnesium flame for untreated wood samples was larger than 16÷20 mm. Instead, after the fire protection treatment of wood with dry mixtures coating, the charcoal depth did not exceed 5÷6 mm. This allows us to conclude that the fire protection of wooden structures and the use of dry mixtures for the localization of magnesium flame is appropriate.

Extinguishing of the magnesium flame with samples of dry mixtures coating with the addition of aluminosilicate microspheres, perlite, basalt scales, metallurgical sludge and ashes in the amount of 10 % showed the intensity of the supply of powder in the extinguishing of magnesium flame in the range of 0.034÷0.041 g/(cm2·s), which is significantly lower than the sodium chloride supply rate. The results of determination of the efficiency of extinguishing magnesium flame with dry mixtures coating indicate the ambiguous effect of fillers on the change in supply rate during flame extinguishing. The greatest effect is demonstrated by the mixture with the addition of basaltic scales, its supply rate is the lowest when extinguishing the magnesium flame and is 0.034 g/(cm2·s)

Author Biographies

Yuriy Tsapko, National University of Life and Environmental Sciences of Ukraine Heroiv Oborony str., 15, Kyiv, Ukraine, 03041 Kyiv National University of Construction and Architecture Povitroflotsky ave., 31, Kyiv, Ukraine, 03037

Doctor of Technical Sciences

V. D. Glukhovsky Scientific Research Institute for Binders and Materials

Аleksii Tsapko, National University of Life and Environmental Sciences of Ukraine Heroiv Oborony str., 15, Kyiv, Ukraine, 03041

Posgraduate student

References

  1. Tsapko, Y., Guzii, S., Remenets, M., Kravchenko, A., Tsapko, O. (2016). Evaluation of effectiveness of wood fire protection upon exposure to flame of magnesium. Eastern-European Journal Enterprise Technologies, 4 (10 (82)), 31–36. doi: 10.15587/1729-4061.2016.73543
  2. Kryvenko, P., Tsapko, Y., Guzii, S., Kravchenko, A. (2016). Determination of the effect of fillers on the intumescent ability of the organic-inorganic coatings of building constructions. Eastern-European Journal of Enterprise Technologies, 5 (10 (83)), 26–31. doi: 10.15587/1729-4061.2016.79869
  3. Tsapko, J., Tsapko, А. (2017). Simulation of the phase transformation front advancement during the swelling of fire retardant coatings. Eastern-European Journal of Enterprise Technologies, 2 (11 (86)), 50–55. doi: 10.15587/1729-4061.2017.73542
  4. Kovalyshyn, V. V., Mirus, O. L., Marych, V. M., Kovalyshyn, V. V., Lozynskyi, R. Ya. (2016). Problemy hasinnia mahniyu ta yoho splaviv. Pozhezhna bezpeka: Zbirnyk naukovykh prats LDU BZhD, 28, 58–63.
  5. Tsapko, Y., Tsapko, А. (2017). Establishment of the mechanism and fireproof efficiency of wood treated with an impregnating solution and coatings. Eastern-European Journal of Enterprise Technologies, 3 (10 (87)), 50–55. doi: 10.15587/1729-4061.2017.102393
  6. Nenahov, S. A., Pimenova, V. P. (2010). Fiziko-himiya vspenivayushchihsya ognezashchitnyh pokrytiy na osnove polifosfata ammoniya (obzor literatury). Pozharovzryvobezopasnost', 19, 11–58.
  7. Kovalyshyn, V. V., Marych, V. M., Kyryliv, Ya. B., Koshelenko, V. V., Mirus, O. L. (2016). Doslidzhennia khimichnykh rechovyn, yak skladnykiv vohnehasnykh poroshkiv dlia hasinnia lehkykh metaliv. Pozhezhna bezpeka: Zbirnyk naukovykh prats LDU BZhD, 29, 46–56.
  8. Carosio, F., Kochumalayil, J., Cuttica, F., Camino, G., Berglund, L. (2015). Oriented Clay Nanopaper from Biobased Components – Mechanisms for Superior Fire Protection Properties. ACS Applied Materials & Interfaces, 7 (10), 5847–5856. doi: 10.1021/am509058h
  9. Krüger, S., Gluth, G. J. G., Watolla, M.-B., Morys, M., Häßler, D., Schartel, B. (2016). Neue Wege: Reaktive Brandschutzbeschichtungen für Extrembedingungen. Bautechnik, 93 (8), 531–542. doi: 10.1002/bate.201600032
  10. Xiao, N., Zheng, X., Song, S., Pu, J. (2014). Effects of Complex Flame Retardant on the Thermal Decomposition of Natural Fiber. BioResources, 9 (3). doi: 10.15376/biores.9.3.4924-4933
  11. Nine, M. J., Tran, D. N. H., Tung, T. T., Kabiri, S., Losic, D. (2017). Graphene-Borate as an Efficient Fire Retardant for Cellulosic Materials with Multiple and Synergetic Modes of Action. ACS Applied Materials & Interfaces, 9 (11), 10160–10168. doi: 10.1021/acsami.7b00572
  12. Cirpici, B. K., Wang, Y. C., Rogers, B. (2016). Assessment of the thermal conductivity of intumescent coatings in fire. Fire Safety Journal, 81, 74–84. doi: 10.1016/j.firesaf.2016.01.011
  13. Fan, F., Xia, Z., Li, Q., Li, Z. (2013). Effects of inorganic fillers on the shear viscosity and fire retardant performance of waterborne intumescent coatings. Progress in Organic Coatings, 76 (5), 844–851. doi: 10.1016/j.porgcoat.2013.02.002
  14. Terebnev, V. V. (2011). Raschet parametrov razvitiya i tusheniya pozharov. Ekaterinburg: izd. Kalan, 460.
  15. Tihonov, V. N. (1973). Analiticheskaya himiya magniya. Moscow: Izd-vo “Nauka”, 254.

Downloads

Published

2017-10-24

How to Cite

Tsapko, Y., & Tsapko А. (2017). Influence of dry mixtures in a coating on the effectiveness of wood protection from the action of a magnesium flame. Eastern-European Journal of Enterprise Technologies, 5(10 (89), 55–60. https://doi.org/10.15587/1729-4061.2017.111106