Thermotechnical properties of the fire-extinguishing powder for extinguishing materials based on magnesium alloy chips

Authors

DOI:

https://doi.org/10.15587/1729-4061.2020.201748

Keywords:

fire-extinguishing powder, metal combustion, magnesium alloys, insulating layer, intensity of extinguishing

Abstract

The article addresses the relevant issue of determining the thermotechnical characteristics of the fire-extinguishing powder for thermal insulation of the fire center of materials based on magnesium alloy chips to prevent fire development and propagation and its effective extinguishing. To solve this problem, laboratory and field experimental studies of the heat-insulating ability of the fire-extinguishing powder of combined effect were conducted. As a result, we obtained the data on the temperature in the center of the fire of materials based on magnesium alloy chips and outside during their suppressing by the fire-extinguishing powder with a combined effect. In this case, the temperature of the non-heated side of the fire-extinguishing powder layer does not exceed 170 °C at the average temperature of the fire center of 740 °C, which indicates high insulation capacity of the powder and, consequently, its high fire-fighting efficiency in extinguishing the fires of materials based on magnesium alloy chips. The obtained temperature data were used to determine the thermophysical parameters of the layer of the fire-fighting powder using the created mathematical model of the heat transfer process in the powder layer at the heat insulation of the fire center. To create a mathematical model of the heat transfer process, the main provisions during consecutive consideration of several experimental situations were stated. The first experimental situation meets the conditions of the stationary thermal process, and other experimental situations meet the conditions of the non-stationary thermal process. These experimental situations were created with the help of changing the thickness of the fire-fighting powder layer at different parameters of its feeding to the fire center. The mathematical model of the process is based on the use of the differential equation of heat transfer at its approximation by the method of finite differences. At the same time, it is believed that the heat transfer conditions at the boundary between the non-heated side of the insulating layer of the fire-extinguishing powder and the environment in each experimental situation are the same.

Using the created model, the coefficient of heat transfer between the non-heated side of the insulating layer of the fire-extinguishing powder and the environment was determined. It amounted to 395.7 W(m2×°С). The dependence of the effective thermal conductivity coefficient on the thickness of the insulating layer was explored. It was shown that this dependence can be approximated by linear dependence l(d)=–0.016+93.907×d (d is the thickness of the layer of the fire-extinguishing powder in meters).

After conducting the necessary calculations, we obtained the value of the required thickness of the layer of fire-extinguishing powder d=45.2 mm

Author Biographies

Bogdan Gusar, Lviv State University of Life Safety Kleparivska str., 35, Lviv, Ukraine, 79007

Adjunct

Department of Emergencies Recovery

Vasyl Kovalyshyn, Lviv State University of Life Safety Kleparivska str., 35, Lviv, Ukraine, 79007

Doctor of Technical Sciences, Professor, Head of Department

Department of Emergencies Recovery

Serhii Pozdieiev, Cherkasy Institute of Fire Safety named after Chernobyl Heroes of National University of Civil Defense of Ukraine Onoprienka str., 8, Cherkasy, Ukraine, 18034

Doctor of Technical Sciences, Professor, Head Researcher

Volodymyr Kovalyshyn, Main Control Service Emergencies Ukraine in Lviv Pidvalna str., 6, Lviv, Ukraine, 79008

PhD, Deputy Head

Oleh Zemlianskyi, Cherkasy Institute of Fire Safety named after Chernobyl Heroes of National University of Civil Defense of Ukraine Onoprienka str., 8, Cherkasy, Ukraine, 18034

PhD, Associate Professor

Department of Automatic Safety Systems and Electrical Installations

Kostiantyn Myhalenko, Cherkasy Institute of Fire Safety named after Chernobyl Heroes of National University of Civil Defense of Ukraine Onoprienka str., 8, Cherkasy, Ukraine, 18034

PhD, Associate Professor, Deputy Head

Department of Automatic Safety Systems and Electrical Installations

References

  1. Kovalyshyn, V., Marych, V., Novitskyi, Y., Gusar, B., Chernetskiy, V., Mirus, O.-Z. (2018). Improvement of a discharge nozzle damping attachment to suppress fires of class D. Eastern-European Journal of Enterprise Technologies, 5 (5 (95)), 68–76. doi: https://doi.org/10.15587/1729-4061.2018.144874
  2. Antonov, A., Stylyk, I. (2013). Test methods for dry chemical powders for the determination of their fire extinguishing capability for D - class of fire. Naukovyi visnyk UkrNDIPB, 2 (28), 242–248. Available at: http://nbuv.gov.ua/UJRN/Nvundipb_2013_2_40
  3. Huo, Y., Zhang, Z.-G., Zou, G.-W. (2020). Experimental study on the thermal flow characteristics of a columnar sodium fire affected by a small amount of fire extinguishing powder in a cylindrical confined space. Applied Thermal Engineering, 170, 114983. doi: https://doi.org/10.1016/j.applthermaleng.2020.114983
  4. Dufaud, O., Bideau, D., Le Guyadec, F., Corriou, J.-P., Perrin, L., Caleyron, A. (2014). Self ignition of layers of metal powder mixtures. Powder Technology, 254, 160–169. doi: https://doi.org/10.1016/j.powtec.2013.11.053
  5. Afzalabadi, A., Poorfar, A. K., Bidabadi, M., Moghadasi, H., Hochgreb, S., Rahbari, A., Dubois, C. (2017). Study on hybrid combustion of aero-suspensions of boron-aluminum powders in a quiescent reaction medium. Journal of Loss Prevention in the Process Industries, 49, 645–651. doi: https://doi.org/10.1016/j.jlp.2017.08.012
  6. Sharma, T. P., Varshney, B. S., Kumar, S. (1993). Studies on the burning behaviour of metal powder fires and their extinguishment: Part II – Magnesium powder heaps on insulated and conducting material beds. Fire Safety Journal, 21 (2), 153–176. doi: https://doi.org/10.1016/0379-7112(93)90040-w
  7. Nam, K.-H., Lee, J.-S. (2018). Study on the effective response method to reduce combustible metal fire. Journal of the Korea Academia-Industrial cooperation Society, 19 (12), 600–606. doi: https://doi.org/10.5762/KAIS.2018.19.12.600
  8. Taveau, J., Vingerhoets, J., Snoeys, J., Going, J., Farrell, T. (2015). Suppression of metal dust deflagrations. Journal of Loss Prevention in the Process Industries, 36, 244–251. doi: https://doi.org/10.1016/j.jlp.2015.02.011
  9. Jiang, H., Bi, M., Li, B., Zhang, D., Gao, W. (2019). Inhibition evaluation of ABC powder in aluminum dust explosion. Journal of Hazardous Materials, 361, 273–282. doi: https://doi.org/10.1016/j.jhazmat.2018.07.045
  10. Hagge, H., Simpson, T., Chattaway, A. (2018). Vermiculite based fire suppression agent. No. 15/935,620. declareted: 26.03.2018; published: 26.08.2019. Available at: https://patents.google.com/patent/US20190290950A1/en
  11. Zemlianskiy, O., Maladyka, I., Miroshnik, O., Shkarabura, I., Kaplenko, G. (2017). Forecasting the emergency explosive environment with the use of fuzzy data. Eastern-European Journal of Enterprise Technologies, 6 (4 (90)), 19–27. doi: https://doi.org/10.15587/1729-4061.2017.116839
  12. Pozdieiev, S., Myhalenko, K., Nuianzin, V., Zemlianskyi, O., Kostenko, T. (2020). Revealing patterns of the effective mechanical characteristics of cellular sheet polycarbonate for explosion venting panels. Eastern-European Journal of Enterprise Technologies, 1 (1 (103)), 32–39. doi: https://doi.org/10.15587/1729-4061.2020.192680
  13. Ognetushitel' poroshkoviy spetsial'niy OPS-5 Diapazon+. Available at: https://www.magazin01.ru/catalog/ognetushiteli/Specialnye-ognetushiteli-klass-D/Ognetushitel-poroshkovyy-specialnyy-OPS-5-z-D-U2/
  14. Class D Stored Pressure Dry Powder Extinguisher. Available at: https://www.amerex-fire.com/products/class-d-stored-pressure-dry-powder-extinguisher/
  15. Ansul Met-L-X Class D Extinguisher Powder, 50 lb pail. Available at: https://www.ansul.com/en/us/DocMedia/F-76230.pdf
  16. Kovalyshyn, V., Marych, V., Gusar, B., Navalianyi, V., Fedyuk, Y. (2019). Jusitfication of dry chemical powders testing procedure. Fire Safety, 33, 53–59. doi: https://doi.org/10.32447/20786662.33.2018.07
  17. Husar, B., Kovalyshyn, V., Marych, V., Lozynskyi, R., Pastukhov, P. (2020). Combined extinguishing of class D, class A and class B fires. Fire Safety, 35, 30–34. doi: https://doi.org/10.32447/20786662.35.2019.05
  18. Isachenko, V. P. et. al. (1981). Teploperedacha. Moscow: «Energoizdat», 415.
  19. Matsevitiy, Yu. M. (2002). Obratnye zadachi teploprovodnosti. Vol. 1: Metodologiya. Kyiv: Naukova dumka, 408.
  20. Beshelev, S. D., Gurvich, F. G. (1980). Matematiko-statisticheskie metody ekspertnyh otsenok. Moscow: Statistika, 263.
  21. Drayzdeyl, D.; Koshmarov, Yu. A., Makarov, V. E. (Eds.) (1990). Vvedenie v dinamiku pozharov. Moscow: Stroyizdat, 424.

Downloads

Published

2020-04-30

How to Cite

Gusar, B., Kovalyshyn, V., Pozdieiev, S., Kovalyshyn, V., Zemlianskyi, O., & Myhalenko, K. (2020). Thermotechnical properties of the fire-extinguishing powder for extinguishing materials based on magnesium alloy chips. Eastern-European Journal of Enterprise Technologies, 2(10 (104), 46–53. https://doi.org/10.15587/1729-4061.2020.201748