Nanorefrigerants application possibilities study to increase the equipment ecological-energy efficiency

Authors

  • Николай Николаевич Лукьянов Odessa National Academy of Food Technologies Kanatnaya, 112, Odessa, Ukraine, 65036, Ukraine
  • Ольга Яковлевна Хлиева Odessa National Academy of Food Technologies Kanatnaya, 112, Odessa, Ukraine, 65036, Ukraine
  • Виталий Петрович Железный Odessa National Academy of Food Technologies Kanatnaya, 112, Odessa, Ukraine, 65036, Ukraine
  • Юрий Владимирович Семенюк Odessa National Academy of Food Technologies Kanatnaya, 112, Odessa, Ukraine, 65036, Ukraine

DOI:

https://doi.org/10.15587/1729-4061.2015.42565

Keywords:

nanoparticles, nanofluids, compressor system, cooling capacity, coefficient of performance, ecological-and-energy analysis

Abstract

The results of experimental and theoretical studies of the TiO2 and Al2O3 nanoparticle additives in the working fluid R600a / mineral oil on the eco-energy efficiency of the compressor system have been considered. The experimental setup (refrigeration compressor system) and the experimental methodology have been described.

Following working fluids have been selected for compressor refrigeration system: R600a / compressor oil; R600a / compressor oil / nanoparticle TiO2 (1,0 and 0,48 wt%.) and R600a / compressor oil / nanoparticles Al2O3 (0,52 and 0,08 wt.%). The results of experimental studies of cooling capacity, compressor power and coefficient of performance at the different values of working fluid flow rate  in the compressor refrigeration system have been reported. It was shown that the nanoparticle additives  may  lead to increase in energy consumption of the compressor system up to 23% at flow rate of the working fluid equal to  0.00025 kg/s at the evaporator temperature 258 K.

The method of eco-energy analysis has been proposed to science-based evaluation of an expediency of nanoparticle additives to the refrigeration equipment working fluids. This method is based on assessment of total equivalent greenhouse gases emissions on the equipment life cycle (TEGHGE).

Expressions to assessment the value of TEGHGE and the specific eco-indicator have been proposed. The values of TEGHGE and eco-indicator on the life cycle of the compressor system based on experimental data obtained for the cooling capacity and compressor power for different working fluids have been analyzed. It was shown that Al2O3 nanoparticle additives with 0.52 % mass concentration provide the best eco-energy effect.

Author Biographies

Николай Николаевич Лукьянов, Odessa National Academy of Food Technologies Kanatnaya, 112, Odessa, Ukraine, 65036

Postgraduate student

The Department of Thermal Physics and Applied Ecology

Ольга Яковлевна Хлиева, Odessa National Academy of Food Technologies Kanatnaya, 112, Odessa, Ukraine, 65036

PhD

The Department of Thermal Physics and Applied Ecology

Виталий Петрович Железный, Odessa National Academy of Food Technologies Kanatnaya, 112, Odessa, Ukraine, 65036

Professor

The Department of Thermal Physics and Applied Ecology

Юрий Владимирович Семенюк, Odessa National Academy of Food Technologies Kanatnaya, 112, Odessa, Ukraine, 65036

Associated Professor

The Department of Thermal Physics and Applied Ecology

References

  1. UNEP 2014. Report of the Refrigeration, air Conditioning and Heat Pumps Technical Options Committee (2014). Assessment. Available at: http://www.montreal-protocol.org/Assessment_Panels/TEAP/Reports/RTOC/RTOC-Assessment-Report-2014.pdf
  2. Zhelezny, V. P. (2014). An application of nanotechnologies in refrigeration – perspectives and challenges. Proc. 11th IIR Gustav Lorentzen Conference on Natural Refrigerants, IIR Hangzhou. China.
  3. Fisher, S. K., Fairchild, P. P., Hughes, P. S. (1990). Global warming implications of replacing CFC. ASHRAE Journal, 34 (4), 14–19.
  4. McCulloch, A. (1994). Life Cycle Analysis to Minimise Global Warming Impact. Renewable energy, 5 (5-8), 1262–1269. doi: 10.1016/0960-1481(94)90160-0
  5. ISO 14040:2006 (2006). Environmental management – Life cycle assessment – Principles and framework.
  6. Zhelezny, V., Hlieva, O., Artemenko, S. (2004). Assessment of Total Equivalent of Greenhouse Gases Emission in the Industry CD Proceedings of the 3rd Europeans Congress “Economics and Management of Energy in Industry”. Lisboa, Portugal.
  7. Zhelezny, V. P., Bykovets, N. P., Khliyeva, O. Ya, Stepanova, V. P., Sukhodol'skaya, A. B. (2004). Method of calculating the total equivalent greenhouse gases emissions in the industry Ekotekhnolohyy y resursosberezhenye [Energy thechnologies & resource saving], 6, 34–43. [in Russian]
  8. UNEP (1987). Montreal Protocol on Substances that Deplete the Ozone Layer. Final Act, 6.
  9. Kyoto Protocol to the United Nations Frame work Convention on Climate Change (1998). United Nations.
  10. Celen, A., Çebi, A., Aktas, M., Mahian, O., Dalkilic, A. S., Wongwises, S. (2014) A review of nanorefrigerants: Flow characteristics and Applications. International Journal of Refrigeration, 44, 125–140. doi: 10.1016/j.ijrefrig.2014.05.009
  11. Efstathios, E. (Stathis) Michaelides (2014). Nanofluidics Thermodynamic and Transport Properties Springer International Publishing Switzerland, 335. doi: 10.1007/978-3-319-05621-0
  12. Nikitin, D., Zhelezny, V., Grushko, V., Ivchenco, D. (2012). Surface tension, viscosity, and thermal conductivity of nanolubricants and vapor pressure of refrigerant/nanolubricant mixtures. Eastern-European Journal of Enterprise Technologies, 5/5 (59), 12–17. Available at: http://journals.uran.ua/eejet/article/view/4566/4230
  13. Zhelezny, V. P., Semenyuk, Yu. V. (2012). Working medium of vapor compression refrigerator: properties, analysis, applications. Odesa: Feniks, 420. [in Russian]
  14. Bi, S., Shi, L., Zhang, L. (2008). Application of nanoparticles in domestic refrigerators. Applied Thermal Engineering, 28, 1834–1843. doi: 10.1016/j.applthermaleng.2007.11.018
  15. Bi, S., Guo, K., Liu, Z., Wu J. (2011). Performance of a domestic refrigerator using TiO2-R600a nano-refrigerant as working fluid. Energy Conversion and Management, 52 (1), 733–737. doi: 10.1016/j.enconman.2010.07.052
  16. Bi, S., Shi, L. (2007). Experimental investigation of a refrigerator with a nano-refrigerant. Journal of Tsinghua University, 47, 1999–2002.
  17. Padmanabhan, V. M. V., Palanisamy, S. (2012). The use of TiO2 nanoparticles to reduce refrigerator ir-reversibility. Energy Conversion and Management, 59, 122–132. doi: 10.1016/j.enconman.2012.03.002
  18. Subramani, N., Prakash, M. J. (2011). Experimental studies on a vapour compression system using nanorefrigerant. International Journal of Engineering, Science and Technology, 3 (9), 95–102. doi: 10.4314/ijest.v3i9.8
  19. Wang, R., Wu, Q., Wu, Y. (2010). Use of nanoparticles to make mineral oil lubricants feasible for use in a residential air conditioner employing hydro-fluorocarbons refrigerants. Energy and Buildings, 42 (11), 2111–2117. doi: 10.1016/j.enbuild.2010.06.023
  20. Jwo, C. S., Jeng, L. Y., Teng, T. P., Chang, H. (2009). Effects of nanolubricant on performance of hydrocarbon refrigerant system. Journal of Vacuum Science & Technology B: Microelectronics and Nanometer Structures, 27 (3), 1473–1477. doi: 10.1116/1.3089373
  21. Kumar, D. S., Elansezhian, R. D. (2012). Experimental Study on Al2O3-R134a Nanorefrigerant in Refrigeration System. International Journal of Modern Engineering Research, 2 (5), 3927–3929.
  22. Sabareesh, R. K., Gobinath, N., Sajith, V., Das, S., Sobhan, C. B. (2012). Application of TiO2 nanoparticles as a lubricant-additive for vapor compression refrigeration systems – An experimental investigation. International Journal Refrigeration, 35 (7), 1989–1996. doi: 10.1016/j.ijrefrig.2012.07.002
  23. Sajumon, K. T., Jubin, V. J., Sreejith, S., Aghil, V. M., Sreeraj Kurup, P. N., Sarath, S. (2013). Performance analysis of nanofluid based lubricant. Proc. of International Conference on Energy and Environment - 2013 (ICEE 2013), 832–838.
  24. Kuleshov, D. K. (2014). Influence of TiO2 nanoparticles on the energy efficiency of the refrigeration machines operating on isobutane. Eastern-European Journal of Enterprise Technologies, 5/8 (71). 47–52. doi: 10.15587/1729-4061.2014.28038
  25. Kuleshov, D. K., Krasnovskiy, I. N. (2014). Experimental Study of the Characteristics of Domestic Refrigerator Using Nanoflyuid R600А/TiO2. Refrigeration Engineering and Technologies, 5 (151), 12–16. doi: 10.15673/0453-8307.5/2014.28690
  26. Zhelezny, V. P., Chen, G. M., Shestopalov, K. O., Melnyk, A. V. (2014). Experimental and theoretical investigation of heat transfer coefficient for boiling of the isobutene/compressor oil solution flow in the pipe. Proc. 11th IIR Gustav Lorentzen Conference on Natural Refrigerants, IIR, Hangzhou. China.
  27. Melnyk, V. A., Nikulin, A. G., Zhelezny, V. P. (2014). The Local Heat Transfer Coefficient Variation at the Boiling of the Isobutane/Compressor Oil Solution Flow in the Pipe. Proceedings of CONV-14: Int. Symp. on Convective Heat and Mass Transfer. Turkey.
  28. Cho, C., Yoo, H. S., Oh, J. M. (2008). Preparation and heat transfer properties of nanoparticle-in-transformer oil dispersions as advanced energy-efficient coolants. Current Applied Physics, 8 (6), 710–712. doi: 10.1016/j.cap.2007.04.060
  29. Independent Statistics and Analysis. Energy Information Administration. Available at: http://www.eia.gov/
  30. World Statistics. Available at: http://world-statistics.org/

Published

2015-06-17

How to Cite

Лукьянов, Н. Н., Хлиева, О. Я., Железный, В. П., & Семенюк, Ю. В. (2015). Nanorefrigerants application possibilities study to increase the equipment ecological-energy efficiency. Eastern-European Journal of Enterprise Technologies, 3(5(75), 32–40. https://doi.org/10.15587/1729-4061.2015.42565

Issue

Section

Applied physics